This wire size calculator guide shows how to pick the right wire size in two steps: first check ampacity, then check voltage drop. Most wrong sizes come from doing only the first step. A wire can carry the current safely and still drop too much voltage over a long run, which leaves a motor slow, a heater weak, or lights dim at the far end.
Picture a small workshop at the back of a garden. The main panel is in the house, the workshop is 100 feet away, and a 20 amp circuit has to run tools there. If you size that wire by amps alone, you will probably pick too small a wire, and the voltage at the workshop will sag every time a tool starts. Size it by both steps, and the same run works quietly for years.
This page picks which AWG to buy.
Step 1: Ampacity, from NEC Table 310.16
Ampacity is the maximum current a conductor can carry continuously without overheating its insulation. This guide uses the 75C column of NEC Table 310.16, the same column the site’s wire size calculator uses. The 75C rating assumes the terminations and equipment are rated for it, so check your equipment markings on a real job. When in doubt, the lower rating governs.
Quick ampacity reference, NEC Table 310.16, 75C column:
| Wire size | Copper | Aluminum |
|---|---|---|
| 14 AWG | 20 A | Not used for branch circuits here |
| 12 AWG | 25 A | 20 A |
| 10 AWG | 35 A | 25 A |
| 8 AWG | 50 A | 35 A |
| 6 AWG | 65 A | 50 A |
| 4 AWG | 85 A | 65 A |
| 2 AWG | 115 A | 90 A |
Step 1 gives you the smallest size whose ampacity is at least your load. That is only half the answer.
Step 2: Voltage drop, with the circular mils formula
To find the size you need, turn the formula around. For the full derivation, see the voltage drop guide.
- Required circular mils = 2 x K x current x one-way length / allowed voltage drop (single-phase and DC)
- Required circular mils = 1.732 x K x current x one-way length / allowed voltage drop (three-phase)
Use the one-way length, not the round trip.
The final answer is the larger of the two steps: the smallest size with enough ampacity, and the smallest size with enough circular mils. Never go below 14 AWG copper or 12 AWG aluminum for branch circuits.

Worked Example A: 20 amps, 100 feet, 120 volts, copper
A 20 amp load, 100 feet one-way, 120 volts single-phase, copper, with a 3 percent limit. Three percent of 120 volts is 3.6 volts allowed.
Step 1: 14 AWG copper is rated 20 amps, so it passes ampacity on paper.
Step 2: required circular mils = 2 x 12.9 x 20 x 100 / 3.6 = 14,333. The 14 AWG conductor has only 4,110 circular mils, and 12 AWG has 6,530, so both fail the voltage drop test. The first size with enough area is 8 AWG copper, with 16,510 circular mils.
Check it: voltage drop = 2 x 12.9 x 20 x 100 / 16,510 = 3.13 volts, which is 2.6 percent of 120 volts, inside the limit. Ampacity is 50 amps, well above the 20 amp load. Answer: 8 AWG copper. Sizing by amps alone would have given 14 AWG, and that wire would have dropped far too much voltage over 100 feet.
Worked Example B: 30 amps, 200 feet, 480 volts, three-phase, copper
A 30 amp load, 200 feet one-way, 480 volts three-phase, copper, with a 3 percent limit. Three percent of 480 volts is 14.4 volts allowed.
Step 1: 10 AWG copper is rated 35 amps, so it passes ampacity.
Step 2: required circular mils = 1.732 x 12.9 x 30 x 200 / 14.4 = 9,310. The first size with enough area is again 10 AWG copper, with 10,380 circular mils.
Check it: voltage drop = 1.732 x 12.9 x 30 x 200 / 10,380 = 12.91 volts, which is 2.7 percent of 480 volts, inside the limit. Answer: 10 AWG copper. Here ampacity and voltage drop agree, which happens on shorter runs and higher voltages, but you only know that once you have checked both.
A quick check you can do in your head
For a 15 amp load over 50 feet at 120 volts, copper, 3 percent allowed: required circular mils = 2 x 12.9 x 15 x 50 / 3.6 = 5,375. That rules out 14 AWG at 4,110 circular mils, and 12 AWG at 6,530 passes, with a drop of 2.96 volts, or 2.5 percent. That matches the calculator result of 12 AWG, and it is a good habit to run one hand check like this before trusting any tool.
Copper versus aluminum
Aluminum has a higher K value, 21.2 against copper at 12.9, and lower ampacity at the same size, so the same job usually needs a larger aluminum wire. Aluminum also needs terminations rated and prepared for aluminum, and antioxidant compound where the manufacturer calls for it. Do not swap materials to save money without checking terminations, lugs, and local code first. See the copper-vs-aluminum feeder example in the voltage drop guide.
Common mistakes
- Sizing by amps alone and ignoring length. This is the most common error, and it shows up as dim lights and struggling motors on long runs, not as a tripped breaker.
- Using the round trip length in the formula. The single-phase and DC formula already doubles for the return conductor, so enter the one-way distance.
- Using the 75C ampacity where the equipment is only rated 60C. The lowest rated part in the chain sets the limit.
- Forgetting that aluminum sizes differently. An aluminum wire of the same AWG number is not equal to the copper wire of the same number.
- Treating the 3 percent figure as a hard code limit. It is an NEC recommendation for good performance, not a pass or fail code rule, but staying inside it is what keeps equipment working properly.
Try it yourself
The site’s wire size calculator runs both steps for you: enter amps, one-way length, voltage, circuit type, and material, and it returns the AWG size with the ampacity and voltage drop checks shown. Use it for the planning stage, and have a licensed electrician confirm the final installation, since local code and equipment ratings can change the answer.
FAQs
What size wire do I need for 20 amps at 100 feet?
At 120 volts single-phase, copper, with a 3 percent voltage drop limit, you need 8 AWG copper. Ampacity alone would suggest 14 AWG, but the voltage drop over 100 feet rules it out. At a different voltage or distance, the answer changes, so run the two steps for your own numbers.
Is copper or aluminum wire size different?
Yes. Aluminum needs a larger size than copper for the same load and length, because it has higher resistance and lower ampacity at the same AWG. It also needs terminations rated for aluminum.
What is the 3 percent voltage drop rule?
It is the NEC recommendation that voltage drop on a branch circuit stay at 3 percent or less, so equipment receives close to its rated voltage. It is a performance recommendation, not a strict code maximum, and the combined feeder and branch circuit recommendation is 5 percent.
Can I use 14 AWG for outlets?
On a 15 amp circuit, 14 AWG copper is the usual minimum, provided the run is short enough that voltage drop stays inside your limit. On a 20 amp circuit, 14 AWG is not enough, since its 75C ampacity is 20 amps only in the simplest reading and code rules for 20 amp branch circuits require 12 AWG copper. Check length and local code before deciding.
Does a higher voltage need a smaller wire?
Usually yes, for the same power and distance. A higher voltage means lower current for the same load, and the allowed voltage drop in volts is also larger, since 3 percent of 480 volts is much bigger than 3 percent of 120 volts. That is why Example B passes with 10 AWG over 200 feet while Example A needs 8 AWG over 100 feet.