You flip on the table saw out in the garage and the shop lights sag for a second. The saw spins up slower than it should, and once it is cutting, it sounds tired. The breaker never trips. Nothing is broken. The problem is the wire run itself: 75 feet of 14-gauge cable between the panel and the garage, and by the time the electricity gets there, several volts have been lost along the way.

That lost voltage has a name, voltage drop, and once you know how to calculate voltage drop with the formula behind it, you can predict exactly what a long run will cost you before you ever pull the wire.

This page calculates how many volts are lost.

What is voltage drop?

Voltage drop is the voltage lost to the resistance of the wire between the source and the load. Every foot of conductor has a little resistance, and current flowing through it turns some of your voltage into heat. The longer the run, the higher the current, and the smaller the wire, the bigger the drop.

A few lost volts might not sound like much, but motors are the first to complain. A motor fed 112 volts instead of 120 runs hotter, starts harder, and lives a shorter life. LED drivers flicker, battery chargers slow down, and heaters put out less than their rating promises. Voltage drop is the invisible tax on every long wire run.

Electrician wiring a breaker panel where voltage drop calculations matter for long wire runs

The voltage drop formula

Here is the whole thing. There are two versions: one for single-phase circuits (your house) and one for three-phase (shops and commercial panels):

Single-phase: VD = 2 × K × I × L ÷ CM

Three-phase: VD = 1.732 × K × I × L ÷ CM

And the percentage, which is the number the NEC cares about:

Percent drop = VD ÷ source voltage × 100

The letters:

  • K is the conductor constant: 12.9 for copper, 21.2 for aluminum. These come from the DC resistance values in NEC Chapter 9, Table 8, at 75°C.
  • I is the load current in amps.
  • L is the one-way length in feet (panel to load, not there and back).
  • CM is the wire’s cross-sectional area in circular mils, also from NEC Chapter 9, Table 8. The common ones: 14 AWG = 4,110; 12 AWG = 6,530; 10 AWG = 10,380; 8 AWG = 16,510; 6 AWG = 26,240.

Why the 2 in the single-phase formula? Because current travels out on one conductor and back on the other, and the formula counts both trips. The three-phase version uses √3 (1.732) instead, because the three phases sit 120 degrees apart. If you want the full backstory on where the K values come from, the IAEI Magazine walkthrough of the voltage drop formulas is the classic reference electricians learn it from.

Step-by-step: calculating voltage drop

Let us work a real one. Say you are running a 120-volt, 15-amp lighting circuit 75 feet (one way) to that garage, on 14 AWG copper.

  1. Write down the four numbers. K = 12.9 (copper). I = 15 amps. L = 75 feet. CM = 4,110 (14 AWG).
  2. Multiply the top. 2 × 12.9 × 15 × 75 = 29,025.
  3. Divide by the wire size. 29,025 ÷ 4,110 = 7.06 volts dropped.
  4. Turn it into a percentage. 7.06 ÷ 120 = 5.89%.

That is nearly double the 3% the NEC recommends for a branch circuit. The lights will dip every time a motor starts.

Try the next size up, 12 AWG (6,530 cmil): 29,025 ÷ 6,530 = 4.44 volts, which is 3.70%. Better, still over 3%.

One more step, 10 AWG (10,380 cmil): 29,025 ÷ 10,380 = 2.80 volts, which is 2.33%. That is the smallest copper size that keeps this run under 3% at a full 15-amp load.

If you would rather skip the arithmetic at the supply house, our voltage drop calculator runs the same NEC math instantly, which is handy when you are comparing sizes on the spot.

Here is a quick reference for a common case: 20 amps at 240 volts on copper, and the farthest each size can go before hitting 3%:

Wire sizeMax one-way distance for 3%
12 AWG91 ft
10 AWG145 ft
8 AWG230 ft
6 AWG366 ft

Notice how doubling the voltage doubles the distance: at 120 volts those runs would be half as long. Higher voltage is the cheapest way to beat voltage drop.

One-way or round trip? The trap that doubles your answer

Here is the trap most beginners fall into. You measure 75 feet from panel to garage, and your instinct says the electricity travels 150 feet, out and back, so you plug 150 into the formula.

Do not. The single-phase formula already counts the return trip; that is what the 2 is for. Enter the one-way distance only. Plug in the round trip and your answer comes out exactly twice as big as it should be, and you will buy wire a size larger than you need on every run.

Copper wire reels showing the conductor sizes used in voltage drop calculations

Copper vs. aluminum on the same run

Aluminum wire is cheaper and lighter, which is why it shows up in feeders and service entrances. But aluminum resists more than copper (K = 21.2 instead of 12.9), so it needs a larger size to hold the same drop. Let us see it on a real run.

A 240-volt, 50-amp single-phase subpanel feed, 100 feet one way.

On 6 AWG copper (26,240 cmil): 2 × 12.9 × 50 × 100 ÷ 26,240 = 129,000 ÷ 26,240 = 4.92 volts, or 2.05%. Under 3%.

On 4 AWG aluminum (41,740 cmil): 2 × 21.2 × 50 × 100 ÷ 41,740 = 212,000 ÷ 41,740 = 5.08 volts, or 2.12%. Also under 3%, but notice it took a whole size larger (4 AWG instead of 6 AWG) to match copper.

Two things to remember with aluminum: size up at least one step compared with copper for the same drop, and make sure every termination (lugs, breakers, connectors) is rated for aluminum. That is where aluminum installations fail, not in the wire itself.

Three-phase: a shop feeder example

Same idea, with √3 in place of the 2. A 208-volt, three-phase load draws 30 amps at the end of a 120-foot run of 10 AWG copper (10,380 cmil). For three-phase, use the line-to-line voltage: 208 here, not 120.

  1. Multiply the top. 1.732 × 12.9 × 30 × 120 = 80,434.
  2. Divide by the wire size. 80,434 ÷ 10,380 = 7.75 volts.
  3. Turn it into a percentage. 7.75 ÷ 208 = 3.73%. Over 3%.

Step up to 8 AWG (16,510 cmil): 80,434 ÷ 16,510 = 4.87 volts, which is 2.34%. That is the fix.

The same current and distance at 480 volts would drop under 2% on the original 10 AWG, which is why commercial feeders run at higher voltages whenever they can.

What the NEC actually says about the 3% rule

The 3% and 5% figures come from informational notes in the National Electrical Code: one under 210.19 for branch circuits, and another under 215.2 for feeders. The recommendation is no more than 3% drop on a branch circuit or a feeder, and no more than 5% for the feeder and branch circuit combined.

“Informational” is doing real work in that sentence. Under NEC 90.5(C), these notes explain but do not enforce, so an inspector cannot fail you on the 3% note alone. But some local amendments, energy codes, and project specifications adopt the 3% figure as a hard requirement, and a few NEC sections do set real limits: sensitive electronic equipment under 647.4(D), and fire pumps under 695.7, where voltage drop becomes a life-safety issue. When in doubt, design to 3% and you will satisfy nearly everyone.

Planning the conduit for a long run like these? Our pipe offset calculator does the bend math, so the wire pull stays smooth after you have sized the conductors.

Common mistakes

  • Entering the round-trip length. One-way distance only: the formula’s 2 already counts the return conductor.
  • Using the breaker size instead of the real load. For a design check, use the expected load current. For a worst case, use the circuit rating.
  • Sizing for drop and forgetting ampacity. Voltage drop never lets you use a smaller wire than the ampacity tables allow. Size for ampacity first, then upsize for drop.
  • Using phase-to-neutral voltage on three-phase. A 208Y/120 V system uses 208 in the three-phase formula, not 120.
  • Expecting the K method to be exact. It ignores reactance and the wire’s real operating temperature. For large conductors, steel raceway, or low power-factor loads, the NEC Chapter 9, Table 9 impedance method is more accurate.

Frequently asked questions

What is the 3% voltage drop rule?

An NEC recommendation (informational notes under 210.19 and 215.2): keep voltage drop under 3% on any branch circuit or feeder, and under 5% for the feeder and branch circuit combined. It is not directly enforceable on its own, but many local codes and job specs adopt it.

How do you calculate voltage drop on a single-phase circuit?

Multiply 2 × K × current × one-way length, then divide by the wire’s circular mils. Use K = 12.9 for copper, 21.2 for aluminum. Divide the result by the source voltage for the percentage. A 120-volt, 15-amp run of 75 feet on 14 AWG copper drops 7.06 volts, or 5.89%.

What size wire do I need for 100 feet at 20 amps?

8 AWG (120V copper, 3% limit) — see how to size a wire.

Does aluminum wire have more voltage drop?

Yes, size for size: aluminum’s K is 21.2 against copper’s 12.9, so the same run drops about 64% more on the same gauge. Go at least one size larger with aluminum, and use terminations rated for it.

How do I reduce voltage drop?

Use a larger conductor, shorten the run, raise the circuit voltage, split the load across more circuits, or run parallel sets on large feeders.

One safety note before you go: this article covers the voltage-drop calculation only. It does not check ampacity, temperature correction, conduit fill, or overcurrent protection. Follow the NEC as adopted in your area, and have a licensed electrician design or verify any installation.