Use this wire size calculator to find the right AWG wire size from load current, one-way length and system voltage, checked against NEC ampacity and voltage drop.
How to size a wire
Wire sizing is a two-step check. Step 1 is ampacity: the conductor must safely carry the load current, so compare your amps with the NEC Table 310.16 ampacity column for your conductor material at 75C and choose the smallest size whose rating covers your load. Step 2 is the voltage-drop check: long runs lose voltage along the wire, so apply K = 12.9 for copper or 21.2 for aluminum and confirm the drop stays within your allowed percentage. The 3 percent recommendation for branch circuits and feeders is the usual target. The correct wire size is the larger of the two steps. When voltage drop forces a bigger wire, its ampacity automatically covers step 1.
Example A: 20-amp, 120-volt branch circuit
A 20A load sits 100 feet away (one way) on a 120V single-phase copper circuit with 3% allowed drop. Ampacity needs at least 20A, which 14 AWG copper meets at 20A, but voltage drop needs 14,334 circular mils, so 12 AWG and 10 AWG are both too small. The calculator recommends 8 AWG copper: the drop is 3.13 V (2.6%, a pass) and the 50A ampacity of 8 AWG covers the 20A load with margin.
Example B: 30-amp, 480-volt three-phase feeder
A 30A load sits 200 feet away (one way) on a 480V three-phase copper feeder with 3% allowed drop. Ampacity needs at least 30A, which 10 AWG copper meets at 35A, and voltage drop needs 9,310 circular mils, which 10 AWG satisfies at 10,380 circular mils. The calculator recommends 10 AWG copper: the drop is 12.92 V (2.7%, a pass) and the 35A ampacity of 10 AWG covers the 30A load.
NEC Table 310.16 ampacity reference (75C)
| Wire size | Copper | Aluminum |
|---|---|---|
| 14 AWG | 20 A | - |
| 12 AWG | 25 A | 20 A |
| 10 AWG | 35 A | 25 A |
| 8 AWG | 50 A | 35 A |
| 6 AWG | 65 A | 50 A |
| 4 AWG | 85 A | 65 A |
| 3 AWG | 100 A | - |
| 2 AWG | 115 A | 90 A |
| 1 AWG | 130 A | - |
| 1/0 AWG | 150 A | 120 A |
| 2/0 AWG | 175 A | 135 A |
| 3/0 AWG | 200 A | - |
| 4/0 AWG | 230 A | 180 A |
Ampacity values are from NEC Table 310.16 at 75C, the same values this calculator uses. The finished installation must also follow terminal temperature ratings, derating for ambient temperature and bundling, and overcurrent protection rules.
Frequently asked questions
What size wire do I need for 20 amps at 100 feet?
For a 120-volt, single-phase copper run carrying 20 amps over 100 feet one way, use 8 AWG copper to stay within 3% voltage drop. The drop works out to about 2.6%, and the 50A rating of 8 AWG covers the 20A load with room to spare. The same run in aluminum needs 6 AWG.
Is aluminum wire sized differently than copper for the same load?
Yes. Aluminum has higher resistance (K = 21.2 versus 12.9 for copper), so it needs a physically larger conductor for the same amps and distance. A run that works on 8 AWG copper typically needs 6 AWG aluminum. Only use connectors and terminations rated for aluminum, and follow the manufacturer's termination guidance.
What is the 3% voltage drop rule?
The NEC recommends, in informational notes, no more than 3% voltage drop on a branch circuit or feeder, and no more than 5% total from the service to the farthest outlet. It is a design recommendation for equipment performance and efficiency rather than a hard limit, but engineers and inspectors treat 3% as the standard target.
Can I use 14 AWG for outlets?
14 AWG copper is standard for 15-amp general receptacle circuits. It cannot be used for 20-amp receptacle circuits, which need 12 AWG copper at minimum, and NEC 240.4(D) limits 14 AWG overcurrent protection to 15 amps in most branch circuits. On long runs, voltage drop can force a larger size anyway.
Related calculators
Browse the construction calculators hub, check a long run with the voltage drop calculator, or read how to calculate voltage drop step by step.